Measuring values | temperature, humidity, depending on the device |
---|
Network technology | LON FT (free topology), RS485 Modbus |
---|
Radio technology | EnOcean (IEC 14543-3-10) |
---|
Frequency | 868 MHz, optional:, 902 MHz (Americas) |
---|
Data transmission | airConfig ready, all types without BUS |
---|
Power supply | 15..24 V = (±10%) or 24 V ~ (±10%) SELV, 240 V: 100..240 V ~ |
---|
Power consumption | typ. 2,0 W (24 V =) | 4,0 VA (24 V ~) |
---|
Measuring range temp. | 0..+50 °C |
---|
Measuring range humidity | 0..100% rH non-condensing |
---|
Accuracy temperature | ±0,5 K (typ. at 21 °C) |
---|
Accuracy humidity | ±3% between 20..80% rH (typ. at 21 °C) |
---|
Inputs | individual configuration for window contact, dew point guard, key card switch, room frequency, alarm, event, 24 V / RS485 Modbus: 4x digital |
---|
Control functions | occupancy signalling, light ON/OFF/DIM, setup scenarios, blinds UP/DOWN/SET, fan stages, setpoint |
---|
Clip | anodized aluminium |
---|
No. of buttons | type L/LQ min. 8 capacitive touch sensor buttons |
---|
Labelling | type L/LQ flexible insert (for up to 8 touch buttons below/beside clip) |
---|
Display | TFT 3,5″, 320×240 px, capacitive touch technology, showing room temperature, setpoint, operation mode, fan stage, occupancy, alarm, date and time, …, ECO note (several steps, red to green; not available for LON), graphic and photo: Instead of date and time individual colour graphics (175×50 or 240×320 pixel) can be shown (e.g. company logo or hotel name; not available for LON), |
---|
Colour | white or black |
---|
Enclosure | PC and glass |
---|
Protection | IP20 according to EN 60529 |
---|
Connection electrical | terminal block, max. 1,5 mm² |
---|
Ambient condition | 0..+50 °C, max. 85% rH non-condensing |
---|
Weight | type S/SQ: 300 g, type L/LQ: 400 g |
---|
Mounting | flush-mounting in standard EU box (Ø=60 mm, min. depth=45 mm) |
---|
Delivery contents | software for configuration (freeware via download) |
---|
Notes | You’ll find the software description at www.thermokon.com, to use the free software airConfig (download) a USB stick, which is able to send and receive EnOcean telegrams, is necessary. The EnOcean USB stick (incl. license) is included in airScan. |
---|