Phoenix Contact, Uninterruptible Power Supply - UPS Systems
Uninterruptible power supply TRIO-UPS-2G/1AC/24DC/10 – 2907161
Phoenix Contact, Uninterruptible Power Supply - UPS SystemsUninterruptible power supply TRIO-UPS-2G/1AC/24DC/10 – 2907161
Uninterruptible power supply with integrated power supply unit.
AGM energy storage with 1.3 Ah to 38 Ah capacity.
Input: 1-phase, output: 24 V DC/10 A. Push-in connection technology
SKU: 2907161
Phoenix Contact, Uninterruptible Power Supply - UPS Systems
Uninterruptible power supply TRIO-UPS-2G/1AC/24DC/10 – 2907161
Uninterruptible power supply with integrated power supply unit.
AGM energy storage with 1.3 Ah to 38 Ah capacity.
Input: 1-phase, output: 24 V DC/10 A. Push-in connection technology
£417.34 (£347.78 ex VAT)
£646.22 (£538.51 ex VAT) for 3 item(s)
2907161 – UPS – Phoenix Contact
Supply DC loads reliably and save space with the TRIO uninterruptible power supplies. An input grid is no longer necessary for startup. Connected industrial PCs can be shut down easily via the integrated USB interface.
Features
- Space saving: Combination of UPS module and power supply in the same housing
- Long buffer times, thanks to large selection of VRLA energy storage systems
- USB interface for connection to higher-level controllers such as industrial PCs
- Startup from energy storage possible, even without mains input
- Universal range of possible applications, thanks to a comprehensive package of approvals and an extended temperature range
- Easy installation, thanks to push-in connection technology
Downloads:
datasheet trio ups 24dc 10A 107432 en 02 (548KB)
Dimensions
Width | 60 mm |
---|---|
Height | 130 mm |
Depth | 115 mm |
Width with alternative assembly | 115 mm |
Height with alternative assembly | 130 mm |
Depth with alternative assembly | 60 mm |
Ambient conditions
Degree of protection | IP20 |
---|---|
Ambient temperature (operation) | -25 °C … 70 °C (> 60 °C Derating: 2.5 %/K) |
Ambient temperature (start-up type tested) | -40 °C |
Ambient temperature (storage/transport) | -40 °C … 85 °C |
Max. permissible relative humidity (operation) | ≤ 95 % (At +25°C, non-condensing) |
Climatic class | 3K3 (in acc. with EN 60721) |
Degree of pollution | 2 |
Installation height | ≤ 4000 m (> 2000 m, observe derating) |
Input data
AC input voltage range | 100 V AC … 240 V AC -15Â % … +10Â % |
---|---|
Inrush current limiting/I²t | < 0.43 A2s |
Mains buffering time | ≥ 15 ms (120 V AC) |
Typical response time | 60 ms |
Input fuse, integrated | 6.3 A (slow-blow, internal) |
Output data
Nominal output voltage | 24 VÂ DC |
---|---|
Setting range of the output voltage (USet) | 24 VÂ DC … 28 VÂ DC (> 24Â V constant capacity) |
Nominal output current (IN) | 5 A |
Dynamic Boost (IDyn.Boost) | 7.5 A |
Derating | > 60 °C (2.5%/K of POut nom.) |
Control deviation | < 0.75 % (Static load change 10Â % … 90Â %) |
Maximum power dissipation in no-load condition | < 3 W (230 V AC) |
Efficiency | typ. 85 % (120 V AC) |
typ. 87 % (230 V AC) | |
typ. 96 % (Battery operation) | |
Residual ripple | < 20 mV |
Connection in parallel | yes, with diode module uncoupled |
Surge protection against internal surge voltages | < 30 VÂ DC |
Feedback voltage resistance | ≤ 35 V DC |
General
Net weight | 0.75 kg |
---|---|
Insulation voltage input/output | 3 kV AC (type test) |
1.5 kV AC (routine test) | |
Protection class | I |
MTBF (IEC 61709, SN 29500) | > 1395470 h (230 V AC, at 25 °C) |
> 825726 h (230 V AC, at 40 °C) | |
> 388314 h (230 V AC, at 60 °C) | |
Mounting position | horizontal DIN rail NS 35, EN 60715 |
Assembly instructions | alignable: horizontally 0Â mm, vertically 50Â mm |
Connection data, input
Connection method | Push-in connection |
---|---|
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 4 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 12 |
Stripping length | 10 mm |
Connection data, output
Connection method | Push-in connection |
---|---|
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 4 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 12 |
Stripping length | 10 mm |
Connection data for signaling
Connection method | Push-in connection |
---|---|
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 1.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 1.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 16 |
Stripping length | 8 mm |
Charging process
Charge characteristic curve | IU0U |
---|---|
Charge current | 0.2 A … 1.5 A (-25 °C … 60 °C) |
Standards
EMC requirements for noise immunity | ENÂ 61000-6-1 |
---|---|
ENÂ 61000-6-2 | |
EMC requirements for noise emission | ENÂ 61000-6-3 |
ENÂ 61000-6-4 | |
Standard – safety for equipment for measurement, control, and laboratory use | IECÂ 61010-1 |
Standard – Safety extra-low voltage | IEC 61010 (SELV) / (PELV) |
Standard – Safe isolation | DINÂ VDEÂ 0100-410 |
Standard – power supply devices for low voltage with DC output | ENÂ 61204-3 |
Conformance/approvals
UL approvals | UL Listed ULÂ 61010 |
---|---|
UL/C-UL Listed ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C |
EMC data
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
---|---|
Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
Conducted noise emission | ENÂ 61000-6-3 (Class B) |
Noise emission | ENÂ 61000-6-3 (Class B) |
DNVÂ GL conducted interference | Class B |
Additional text | Area power distribution |
DNVÂ GL noise radiation | Class B |
Additional text | Bridge and deck area |
Electrostatic discharge | EN 61000-4-2 |
Contact discharge | 6 kV (Test Level 4) |
Discharge in air | 8 kV (Test Level 4) |
Electromagnetic HF field | ENÂ 61000-4-3 |
Frequency range | 80 MHz … 6 GHz |
Test field strength | 10 V/m (Test Level 3) |
Comments | Criterion B |
Fast transients (burst) | ENÂ 61000-4-4 |
Input | 4 kV (Test Level 4 – asymmetrical) |
Output | 2 kV (Test Level 3 – asymmetrical) |
Signal | 1 kV (Test Level 4 – asymmetrical) |
Comments | Criterion B |
Input | 2 kV (Test Level 3 – symmetrical) |
4 kV (Test Level 4 – asymmetrical) | |
Output | 1 kV (Test Level 1 – symmetrical) |
2 kV (Test Level 3 – asymmetrical) | |
Signal | 1 kV (Test Level 2 – asymmetrical) |
Comments | Criterion B |
Conducted interference | ENÂ 61000-4-6 |
I/O/S | asymmetrical |
Frequency range | 0.15 MHz … 80 MHz |
Voltage | 10 V (Test Level 3) |
Comments | Criterion A |
Attenuated sinusoidal oscillations (ring wave) | EN 61000-4-12 |
Input | 2 kV (symmetrical) |
4 kV (asymmetrical) | |
Comments | Criterion B |
Criterion A | Normal operating behavior within the specified limits. |
Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |