Uninterruptible power supply TRIO-UPS-2G/1AC/24DC/5 – 2907160


Uninterruptible power supply with integrated power supply unit.

AGM energy storage with 1.3 Ah to 12 Ah capacity.

Input: 1-phase, output: 24 V DC/5 A. Push-in connection technology

 

 

£325.40 (£271.17 ex VAT)

£554.28 (£461.90 ex VAT) for 3 item(s)

2907160 – UPS – Phoenix Contact

Supply DC loads reliably and save space with the TRIO uninterruptible power supplies. An input grid is no longer necessary for startup. Connected industrial PCs can be shut down easily via the integrated USB interface.

Features

  • Space saving: Combination of UPS module and power supply in the same housing
  • Long buffer times, thanks to large selection of VRLA energy storage systems
  • USB interface for connection to higher-level controllers such as industrial PCs
  • Startup from energy storage possible, even without mains input
  • Universal range of possible applications, thanks to a comprehensive package of approvals and an extended temperature range
  • Easy installation, thanks to push-in connection technology

Downloads:

datasheet trio ups 24dc 5A 107431 en 02 (544KB)

 

Dimensions

Width 60 mm
Height 130 mm
Depth 115 mm
Width with alternative assembly 115 mm
Height with alternative assembly 130 mm
Depth with alternative assembly 60 mm

Ambient conditions

Degree of protection IP20
Ambient temperature (operation) -25 °C … 70 °C (> 60 °C Derating: 2.5 %/K)
Ambient temperature (start-up type tested) -40 °C
Ambient temperature (storage/transport) -40 °C … 85 °C
Max. permissible relative humidity (operation) ≤ 95 % (At +25°C, non-condensing)
Climatic class 3K3 (in acc. with EN 60721)
Degree of pollution 2
Installation height ≤ 4000 m (> 2000 m, observe derating)

Input data

AC input voltage range 100 V AC … 240 V AC -15 % … +10 %
Inrush current limiting/I²t < 0.43 A2s
Mains buffering time ≥ 15 ms (120 V AC)
Typical response time 60 ms
Input fuse, integrated 6.3 A (slow-blow, internal)

Output data

Nominal output voltage 24 V DC
Setting range of the output voltage (USet) 24 V DC … 28 V DC (> 24 V constant capacity)
Nominal output current (IN) 5 A
Dynamic Boost (IDyn.Boost) 7.5 A
Derating > 60 °C (2.5%/K of POut nom.)
Control deviation < 0.75 % (Static load change 10 % … 90 %)
Maximum power dissipation in no-load condition < 3 W (230 V AC)
Efficiency typ. 85 % (120 V AC)
typ. 87 % (230 V AC)
typ. 96 % (Battery operation)
Residual ripple < 20 mV
Connection in parallel yes, with diode module uncoupled
Surge protection against internal surge voltages < 30 V DC
Feedback voltage resistance ≤ 35 V DC

General

Net weight 0.75 kg
Insulation voltage input/output 3 kV AC (type test)
1.5 kV AC (routine test)
Protection class I
MTBF (IEC 61709, SN 29500) > 1395470 h (230 V AC, at 25 °C)
> 825726 h (230 V AC, at 40 °C)
> 388314 h (230 V AC, at 60 °C)
Mounting position horizontal DIN rail NS 35, EN 60715
Assembly instructions alignable: horizontally 0 mm, vertically 50 mm

 

Connection data, input

Connection method Push-in connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 4 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 12
Stripping length 10 mm

Connection data, output

Connection method Push-in connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 4 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 12
Stripping length 10 mm

 

Connection data for signaling

Connection method Push-in connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 1.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 1.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 16
Stripping length 8 mm

Charging process

Charge characteristic curve IU0U
Charge current 0.2 A … 1.5 A (-25 °C … 60 °C)

 

Standards

EMC requirements for noise immunity EN 61000-6-1
EN 61000-6-2
EMC requirements for noise emission EN 61000-6-3
EN 61000-6-4
Standard – safety for equipment for measurement, control, and laboratory use IEC 61010-1
Standard – Safety extra-low voltage IEC 61010 (SELV) / (PELV)
Standard – Safe isolation DIN VDE 0100-410
Standard – power supply devices for low voltage with DC output EN 61204-3

Conformance/approvals

UL approvals UL Listed UL 61010
UL/C-UL Listed ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C

EMC data

Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
Conducted noise emission EN 61000-6-3 (Class B)
Noise emission EN 61000-6-3 (Class B)
DNV GL conducted interference Class B
Additional text Area power distribution
DNV GL noise radiation Class B
Additional text Bridge and deck area
Electrostatic discharge EN 61000-4-2
Contact discharge 6 kV (Test Level 4)
Discharge in air 8 kV (Test Level 4)
Electromagnetic HF field EN 61000-4-3
Frequency range 80 MHz … 6 GHz
Test field strength 10 V/m (Test Level 3)
Comments Criterion B
Fast transients (burst) EN 61000-4-4
Input 4 kV (Test Level 4 – asymmetrical)
Output 2 kV (Test Level 3 – asymmetrical)
Signal 1 kV (Test Level 4 – asymmetrical)
Comments Criterion B
Input 2 kV (Test Level 3 – symmetrical)
4 kV (Test Level 4 – asymmetrical)
Output 1 kV (Test Level 1 – symmetrical)
2 kV (Test Level 3 – asymmetrical)
Signal 1 kV (Test Level 2 – asymmetrical)
Comments Criterion B
Conducted interference EN 61000-4-6
I/O/S asymmetrical
Frequency range 0.15 MHz … 80 MHz
Voltage 10 V (Test Level 3)
Comments Criterion A
Attenuated sinusoidal oscillations (ring wave) EN 61000-4-12
Input 2 kV (symmetrical)
4 kV (asymmetrical)
Comments Criterion B
Criterion A Normal operating behavior within the specified limits.
Criterion B Temporary impairment to operational behavior that is corrected by the device itself.